arXiv:2609.03154cs.ETSep 2026

Manuscript Offprint

arXiv:2609.03154

Embedding Single-Phase Grid-Forming Inverters in Three-Phase Unbalanced Power Flow

Kamini Shahare, Fei Feng, Peng Zhang

Kamini Shahare, Fei Feng, and Peng Zhang

Abstract—This letter introduces Grid-Forming Three-Phase Power Flow (GFM-3PF), an augmented Newton power flow framework for modeling single-phase grid-forming inverters (GFMs) in three-phase unbalanced networks. The contributions of this work are threefold: 1) developing a two-stage solution strategy based on positive-sequence initialization followed by three-phase phase-domain lifting for robust large-scale computation; 2) incorporating phase-domain unbalanced network modeling with controlled mutual coupling together with phase-dependent, frequency-sensitive load representation; and 3) embedding a single-phase GFM bus model directly into the three-phase unbalanced Newton power flow equations through a common droop-governed frequency state. GFM-3PF is validated on 3-bus, 33-bus, and 118-bus test systems, demonstrating its accuracy, robustness, and scalability.

Index Terms—Grid-forming inverter, three-phase unbalanced power flow, augmented Newton method, frequency-sensitive load.

I. INTRODUCTION

Conventional power flow formulations are increasingly challenged by inverter-based resources, three-phase unbalance, and reduced synchronous generation [1]. Grid-forming inverters (GFMs) in low-inertia systems are crucial because their steady-state operating point is governed by droop control and cannot be correctly represented by standard slack or PV buses [2]. Although existing three-phase power flow methods capture asymmetric loading and phase coupling [3], a unified formulation that embeds droop-controlled single-phase GFM behavior into three-phase network equations remains needed [4].

This letter presents Grid-Forming Three-Phase Power Flow (GFM-3PF), an augmented Newton framework that enforces the single-phase GFMs droop equations directly in the Newton residual. Unlike conventional three-phase power flow with fixed frequency, GFM-3PF solves the phase-domain voltage profile and droop-governed frequency simultaneously, capturing the coupling among unbalanced loading, single-phase GFM injection, and frequency-sensitive demand.