Manuscript Offprint
arXiv:2609.03165QSVT-Based Three-Phase Unbalanced Power Flow
Kamini Shahare and Peng Zhang
Abstract—This letter introduces QSVT-3PF, a quantum singular value transformation (QSVT) based solver for three-phase unbalanced power flow with embedded single-phase grid-forming inverter (GFM) operation. The contributions are threefold: 1) reformulating the Newton correction as a QSVT-compatible inverse problem using a normalized block-encoded phase-domain Jacobian; 2) introducing a regularized singular-value filter to improve robustness under ill-conditioned and stressed operating conditions; and 3) validating the proposed solver on an IEEE 5-bus system and the IEEE 123-node test feeder with single-phase GFM integration. Test results show that QSVT-3PF matches the classical Newton benchmark in residual convergence, voltage profile, and final operating point, demonstrating the feasibility of QSVT-3 for large unbalanced distribution systems.
Index Terms—Quantum singular value transformation, quantum power flow, three-phase unbalanced power flow, grid-forming inverter.
I. INTRODUCTION
As distribution networks become larger, more unbalanced, and more inverter-dominated, scalable alternatives to classical three-phase power flow are increasingly attractive. Quantum computing provides a promising pathway to accelerate grid analytics such as power flow [1], [2]. Existing quantum power flow studies have primarily considered HHL-type methods or variational quantum linear solvers [3]. However, HHL requires demanding assumptions on state preparation and circuit depth, while variational methods depend on classical optimization and may suffer from trainability limitations.
Quantum singular value transformation (QSVT) provides a general framework for implementing matrix functions through polynomial transformations of the singular values of a block-encoded matrix [4]. Since Newton-based power flow repeatedly requires the inverse action of the Jacobian on the residual vector, QSVT is well suited for developing a quantum-compatible power flow solver.
This letter proposes QSVT-3PF, a quantum singular value transformation-based solver for three-phase unbalanced power flow with embedded single-phase grid-forming inverter operation. The main contributions are summarized as follows:
-
We reformulate the Newton correction for three-phase power flow as a QSVT-compatible matrix-inversion problem with a normalized block-encoded Jacobian.
-
We develop a polynomial inverse singular-value filter with regularized QSVT updates to compute robust Newton corrections without variational optimization.
-
We validate the proposed QSVT-3PF solver on the IEEE 5-bus system and IEEE 123-node test feeder with single-phase GFM integration, demonstrating its applicability to unbalanced inverter-dominated distribution networks.
Let denote the energized bus phases and let be the phase-domain voltage vector. The real-valued augmented residual is
where denotes the GFM droop-frequency residual.
At each Newton iteration, the correction satisfies . The inverse action of this augmented three-phase Jacobian is the computational bottleneck and is to be replaced by the proposed QSVT-based singular-value filtering step as follows.
III. QSVT-BASED NEWTON CORRECTION
The key objective of QSVT-3PF is to approximate the Newton correction using quantum singular value transformation.
A. Jacobian Normalization
The Jacobian is first normalized as
where
This normalization guarantees that the singular values of lie within .
Let the singular value decomposition of be
where
The exact inverse action can be written as
Therefore, the Newton correction becomes
This material is based upon work supported by the National Science Foundation under Grant Number 2432387.
K. Shahare and P. Zhang are with the Department of Electrical and Computer Engineering, Stony Brook University, Stony Brook, NY 11794-2350, USA (e-mail: kamini.shahare, p.zhang@stonybrook.edu).
B. QSVT Inverse Polynomial
QSVT implements the desired singular-value transformation through a polynomial approximation. For Newton power flow, the target operation is the inverse singular-value map, . Since direct inversion becomes ill-conditioned near zero, the approximation is restricted to the well-conditioned interval and represented as
Using this polynomial filter, the inverse action of the normalized Jacobian is approximated as
Thus, the QSVT-based Newton correction is
C. Regularized QSVT Filter
For ill-conditioned cases, a regularized inverse filter is used to suppress small singular-value amplification:
The regularized QSVT Newton correction is
IV. QUANTUM BLOCK-ENCODING FORMULATION
To implement QSVT, the normalized Jacobian is embedded into a larger unitary operator. A block encoding of is defined as a unitary satisfying
where a is the number of ancilla qubits.
Given this block encoding, QSVT constructs a sequence of alternating applications of , , and single-qubit phase rotations:
where phase angles are chosen so that the resulting SVT implements the polynomial .
The effective action of the QSVT circuit is
When applied to the encoding of the residual vector,
the QSVT circuit produces a state proportional to
After rescaling by , the resulting vector approximates the Newton correction:
Algorithm 1 QSVT-3PF Solver
1: Input: , load data, GFM droop, , ,
2: Output: and residual history
3: Initialize
4: for do
5: Compute , , and residual
6: if then
7: break
8: end if
9: Form the three-phase Jacobian
10: Normalize ,
11: Apply either the inverse filter or the regularized filter
12: Compute the QSVT Newton correction:
13: Update
14: Recover from
15: end for
16: return and
V. TEST CASE SCENARIOS
We validate QSVT-3PF on two test systems: an IEEE 5-bus system and the IEEE 123-node test feeder. The IEEE 5-bus system is used to verify the QSVT inverse approximation in a compact network, while the IEEE 123-node feeder is used to evaluate the method under feeder-scale three-phase unbalanced conditions with single phase GFM.
A. IEEE 5-Bus System
The IEEE 5-bus system is used as a compact benchmark to verify the basic performance of the proposed QSVT-3PF solver before applying it to larger unbalanced feeders. The system is modeled in three-phase coordinates with a single-phase GFM inverter connected at Bus 5, Phase A. This small case allows the iteration-wise behavior of the QSVT-based inverse approximation to be clearly observed and directly compared with the classical Newton solution.
As shown in Fig. 1, the Classical Newton PF and Quantum QSVT PF exhibit nearly identical convergence behavior. Both solvers reach the same final voltage profile and droop-regulated frequency, confirming that the QSVT singular-value filtering step produces an equivalent Newton correction for the augmented three-phase Jacobian. The close overlap of the voltage magnitudes further verifies that the QSVT-3PF formulation preserves the classical steady-state operating point while replacing the direct linear solve with a polynomial inverse approximation.
B. IEEE 123-Node Test Feeder
The IEEE 123-node test feeder is used as the large-scale unbalanced benchmark to evaluate the scalability of the proposed QSVT-3PF solver. Compared with the IEEE 5-bus case, this feeder includes a larger number of voltage nodes, phase-specific laterals, and highly unbalanced loading, making it

Fig. 1. IEEE 5-bus system: convergence and voltage magnitude comparison between classical Newton and QSVT-3PF.
suitable for feeder-scale validation. Fig. 2 shows the feeder-wide voltage magnitude profile obtained using the proposed QSVT-3PF solver for the IEEE 123-node test feeder.
Table I presents the iteration-wise comparison of Quantum QSVT PF and Classical Newton PF for three representative GFM-connected voltage quantities, , , and , along with the frequency variable . These monitored quantities are selected from different feeder locations and phases to evaluate whether the QSVT inverse approximation preserves the classical Newton update across the unbalanced network. Both solvers produce identical values at every iteration and converge at the fourth iteration to pu, pu, pu, and pu. The identical trajectories verify that the QSVT singular-value filter accurately reproduces the Newton correction and preserves the final operating point of the IEEE 123-node feeder.
TABLE I
ITERATION-WISE COMPARISON OF QUANTUM QSVT PF AND CLASSICAL NEWTON PF
| Algorithm | Iteration | ||||
|---|---|---|---|---|---|
| Quantum QSVT PF | 1 | 0.9597 | 1.0001 | 0.9858 | 0.9985 |
| 2 | 0.9987 | 1.0403 | 1.0261 | 0.9998 | |
| 3 | 0.9979 | 1.0395 | 1.0254 | 0.9998 | |
| 4 | 0.9979 | 1.0395 | 1.0254 | 0.9998 | |
| Classical Newton PF | 1 | 0.9597 | 1.0001 | 0.9858 | 0.9985 |
| 2 | 0.9987 | 1.0403 | 1.0261 | 0.9998 | |
| 3 | 0.9979 | 1.0395 | 1.0254 | 0.9998 | |
| 4 | 0.9979 | 1.0395 | 1.0254 | 0.9998 |
Fig. 3 presents the probability distributions of voltage magnitudes at the GFM-connected buses. These histograms provide a statistical view of the voltage concentration around the converged operating point. The close agreement between the classical Newton and QSVT-based distributions indicates that the QSVT inverse approximation preserves the voltage solution at the GFM buses and does not introduce noticeable numerical dispersion. Since the QSVT solution produces nearly the same concentration pattern as the classical Newton solution, the dominant voltage states are preserved after the singular-value filtering process. This confirms that the reduced quantum inverse-filter step remains consistent with the full Newton-based feeder solution.

Fig. 2. IEEE 123-node test feeder: voltage magnitude profile obtained using the proposed QSVT-3PF solver.

Fig. 3. Probability distribution of voltage magnitudes at GFM buses.
VI. CONCLUSION
This letter demonstrates that three-phase unbalanced power flow can be recast from a direct Newton solve into a singular-value filtering problem. In practice, the network equations and the three-phase Jacobian are formed in the same way as in a classical Newton power-flow program; only the Jacobian-solve step used to compute the voltage correction is replaced by the QSVT inverse filter. The new QSVT-3PF formulation therefore provides a quantum path to preserve Newton-like accuracy while enabling spectral regularization of ill-conditioned operating points. Particularly, its regulation of weak singular directions of the Jacobian makes it well suited for stressed, unbalanced, and inverter-rich feeders.
In sum, QSVT-3PF offers a reusable computational primitive for repeated grid analytics, such as feasible operating region analysis, DER hosting studies, and future quantum-enabled digital twins for distribution grids.
REFERENCES
[1] Y. Zhou, et al. "Quantum computing in power systems," iEnergy, vol. 1, no. 2, pp. 170-187. Jun. 2022.
[2] F. Feng, Y. Zhou, and P. Zhang, "Quantum power flow," IEEE Transactions on Power Systems, vol. 36, no. 4, pp. 3810–3812, Jul. 2021.
[3] R. Fan, C. Lin, and P. Zhang, "Quantum Newtonian power flow," IEEE Transactions on Power Systems, vol. 41, no. 1, pp. 777–780, Jan. 2026.
[4] A. Gilyén, Y. Su, G. H. Low, and N. Wiebe, "Quantum singular value transformation and beyond: exponential improvements for quantum matrix arithmetic," in Proc. 51st ACM Symposium on Theory of Computing, 2019, pp. 193–204.
[5] K. Shahare, F. Feng, and P. Zhang, "Embedding Single-Phase Grid-Forming Inverters in Three-Phase Unbalanced Power Flow," IEEE PES Letters, 2026, submitted.