arXiv:2609.03297cs.DCSep 2026

Manuscript Offprint

arXiv:2609.03297

A Technique for Load Shifting Low-latency Applications in Multi-Region Renewables Harvesting via SMT Core Pooling

Tharindu B. Hewage, Shashikant Ilager, Maria A. Rodriguez, Rajkumar Buyya

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

Tharindu B. Hewage, Shashikant Ilager, Maria A. Rodriguez, and Rajkumar Buyya

Abstract—Load shifting across geographic regions to chase intermittent renewable energy availability is commonly used in reducing cloud infrastructure carbon footprint. However, it often omits low-latency applications due to high latency variances of wide area networks (WAN) that interconnect regions. This paper addresses accommodating low-latency applications into load shifting by minimizing their shifting across the WAN. We propose a technique using a hardware-software co-design approach. At the hardware level, we conduct server load matching over renewables supply peaks and valleys by deep idling physical cores in two otherwise identical server pools, with one enabling simultaneous multi-threading (SMT) in CPUs. In return, we achieve a static set of logical cores amidst energy supply dynamics, reducing the probability of workload shifting. At the software level, we efficiently chase the static set of cores for low-latency applications within regions while prioritizing best-effort applications to accommodate shifting requirements across WANs. Our approach exploits the lower performance compromise of SMT cores due to their hardware multi-threading. We implement the proposed technique with OpenStack and CPU idle states and evaluate its performance on a real experimental testbed with Azure VM arrival traces. Results show an 80% reduction in offloading low-latency VMs and a 43.81% reduction in coefficient of variation of p90 end-user latency while having a worst-case latency compromise of 11.97% due to SMT cores.

Index Terms—Carbon-aware computing, low-latency applications, cloud computing, load shifting, renewable energy.

I. INTRODUCTION

The data center industry is expected to reach nearly 13% of global electricity demand by 2030 [1]. With electricity generation being one of the most significant contributions to global CO2CO_{2} emissions [2], data center operators are presented with the challenge of grid decarbonization. Cloud data center fleets are often spatially distributed and powered by sources integrated with intermittent renewables, emitting varying amounts of CO2CO_{2} per kilowatt-hour (kWh) [3]. As a result, carbon optimization in cloud computing infrastructures predominantly relies on load shifting—shifting workloads across data center locations via cloud Virtual Machine (VM) scheduling [3]–[7]—to chase availability of renewables for workload execution. Adversely, network traffic among spatially distributed data centers can hop through Wide Area Networks (WAN) with high latency variances [8], resulting in unpredictable end-user latency performances in VMs. For instance, when aggregated network traffic of VMs reaches edge routers of WAN, traffic management at the IP layer that is unaware of the aggregation can split them into tunnels with different latency performances [8]. To avoid potential application performance degradation from such unpredictable latency performances, cloud providers often limit load shifting to best-effort workloads with flexible latency requirements, such as scientific simulations, batch processing, and machine learning training [3]. To this end, this work explores the opportunities in accommodating low-latency

workloads for cloud load shifting, emphasizing minimizing the high latency variance that VMs experience during load shifting.

Use cases of cloud low-latency computing are emerging across various industries, including healthcare, factories, automotive, and aviation [9]. According to recent forecasts, they are predicted to accommodate nearly 30% of the world's data in the near term [10]. Today, low-latency computing plays a vital role in content delivery networks, streaming applications, and applications of recent AI-boom, such as serving generative AI models. Figure 1 illustrates a spectrum of such applications available in the cloud according to their latency service level agreements (SLAs). Preserving latency SLAs is imperative to maintain application service quality, whereas accommodating the growing low-latency applications in load shifting is equally important for the sustainable growth of clouds. The key challenge is the workload impact from cloud network overheads. At renewables supply valleys, the data center's workload must be migrated to match the server's reduced resource capacity. As migrations often move workloads across WANs, workloads are then susceptible to WAN's high latency variances. Existing techniques for load shifting either compromise latency performance with potential server performance throttling [11] or do not consider opportunities in limiting workload migration within the data center.

To address these gaps, we propose a technique that aims to contain low-latency applications within the local cloud region. We leverage a hardware-software co-design approach. At the hardware level, we tackle the server resource capacity reduction problem in renewable supply valleys. We apply an application-independent CPU core-level power management mechanism with two heterogeneous server pools. CPUs in server pools are physically the same, yet one enables simultaneous multi-threading (SMT) to double the available server logical cores through hardware multi-threading. During supply valleys, half of the CPU cores are set to deep idle and restored at the peaks. In return, we maintain a static set of logical cores across the server pools. At supply valleys, servers of the SMT pool exhibit the static set, whereas the servers of the non-SMT pool exhibit the static set at supply peaks. At the software level, we dynamically chase the static set of logical cores across the server pools for low-latency workloads. In our technique, load shifting for low-latency workloads is mostly conducted within the local cloud region using its fast network fabric, eliminating the communication overheads of WAN. Further, executing low-latency workloads in the SMT pool incurs only a minimum performance overhead since SMT cores use hardware multi-threading, which provides better performance.

We implement our technique with OpenStack and core-level power management with CPU idle states. To evaluate, we

Figure

Fig. 1. Low-latency applications in cloud data centers [12].

Figure

Fig. 2. Average operational gross carbon emissions per unit of energy from the power grid across Google cloud regions [13].

use an experimental cloud region with SMT server pooling and a local network fabric. We use an HP ProLiant server for each pool with a 12-core Intel Xeon silver CPU. We enable SMT through Intel Hyper-threading technology. We use VM arrival data from Azure's workload traces and renewable dynamics from ELIA solar data. We measure low-latency performance inside VMs by running the Cyclictest tool. The key contributions of our work are as follows:

(1) Propose a new technique for localized load shifting of low-latency workloads to integrate renewable energy, avoiding the latency compromises of workload shifting over WANs across geographical regions.

(2) Implement the proposed technique in real cloud settings and conduct detailed experiments using production VM and renewable energy data.

(3) Evaluate the proposed technique against state-of-the-art baselines, focusing on maintaining low-latency performance. Our results show an 80% reduction in offloading low-latency VMs, a 43.81% reduction in coefficient of variation of p90 end-user latency, and an 11.97% performance compromise due to SMT cores.

References (33)