Energy consumption is one of the largest operational expenditure items for mobile network operators, yet site-level energy inefficiencies such as faulty cooling controllers, idle radio equipment, and parasitic auxiliary loads often remain undetected because no ground-truth inefficiency labels exist and historical measurements may already contain embedded inefficiencies. This study proposes an unsupervised peer-relative approach based on the premise that sites with similar structural and operational characteristics should exhibit comparable energy consumption. To capture these relationships, a novel energy-aware Minimum Distortion Embedding (MDE) formulation is introduced that extends the standard MDE objective with an energy-based repulsion mechanism. This encourages sites with anomalously high energy consumption relative to comparable peers to become displaced from their local neighbourhoods in the embedding space. The resulting low-dimensional representation simultaneously preserves structural similarity and encodes energy-related deviations, enabling the identification of potentially inefficient sites through peer-relative comparison. The derived anomaly scores provide a practical mechanism for prioritising field investigations, allowing mobile network operators to focus engineering resources on sites most likely to yield energy savings. Experimental results demonstrate that the proposed approach outperforms conventional anomaly detection baselines and provides a robust foundation for large-scale energy-efficiency optimisation in mobile networks.

Keywords— Anomaly detection, energy efficiency, green communications, minimum-distortion embedding, mobile networks, representation learning, unsupervised learning.

*E. N. Koto is with the African Institute for Mathematical Sciences (AIMS), Cape Town, South Africa (e-mail: eliuad@aims.ac.za). †J. du Toit is with Technology Strategy Planning Architecture & Assurance, Vodacom Group Limited, South Africa, and the Department of Electrical and Electronic Engineering, Stellenbosch University, South Africa, (e-mail: jacowp357@gmail.com) ‡A. Stoltz is with Technology Strategy Planning Architecture & Assurance, Vodacom Group Limited, South Africa, and School of Computer Science and Applied Mathematics, University of the Witwatersrand, South Africa, (e-mail: Adham.Stoltz@vodacom.co.za). §J. du Preez is with the Department of Electrical and Electronic Engineering, Stellenbosch University, Stellenbosch, South Africa (e-mail: jadupreez@gmail.com). This work was supported in part by a Google DeepMind Scholarship at AIMS South Africa.

1 Introduction

The rapid growth of mobile communications has driven a substantial expansion of the infrastructure operated by mobile network operators (MNOs). Modern networks comprise thousands of geographically distributed sites, each a complex cyber-physical system combining radio access network (RAN) equipment including antennas, remote radio units (RRUs), baseband units (BBUs), and transmission hardware, with supporting infrastructure such as rectifiers, backup batteries, power conversion equipment, remote management systems, and thermal management systems (Fig. 1). The cumulative energy demand of these sites constitutes a major component of MNO operational expenditure and a growing sustainability concern as electricity prices rise, carbon-reduction commitments tighten, and network densification continues [1, 2]. Because base station sites dominate network energy consumption, even modest site-level efficiency improvements translate into substantial financial and environmental savings when scaled across a national network.

Figure

Figure 1: High-level component layout of a typical mobile network site. Radio and signal processing equipment provide the communication functions, while supporting subsystems such as cooling and power conversion contribute a large proportion of the site's overall energy consumption.

A significant share of site energy is consumed by supporting subsystems rather than by the radios themselves. Thermal management is a prominent example: radio, power, and electronic components generate heat inside equipment enclosures, and cooling systems must keep them within safe operating temperatures [3]. Measurements at an operational site in South Africa showed that cooling alone accounted for approximately 40% of total site energy consumption while a single air conditioner was active [4]. Faults in these subsystems, such as a controller that fails to switch off an air conditioner, a degraded rectifier, parasitic auxiliary loads, or radio equipment drawing near-peak power under low utilisation, can waste energy persistently without causing service interruptions, and therefore remain unnoticed for long periods.

Traditional approaches to reducing site energy consumption have primarily focused on engineering interventions, including designing and validating improved physical site configurations in laboratory or test environments before rolling them out across the network, as well as optimising parameters on active network equipment. While these approaches have delivered substantial improvements, they assume that similar optimisations can be broadly applied across sites. In practice, however, every mobile network site exhibits a unique combination of characteristics, including its equipment configuration, physical layout, environmental exposure, local weather conditions, traffic demand, and operational history. These factors interact to produce highly site-specific energy consumption behaviour, making it difficult to directly compare measured electricity consumption with billing records or identify genuine opportunities for optimisation from absolute energy usage alone.

Detecting such inefficiencies from operational data is difficult for three reasons. First, there are typically no labels indicating whether a site operates efficiently: monthly energy readings blend normal operation with possible abnormal behaviour, ruling out conventional supervised learning [5]. Second, models trained to predict historical consumption may absorb long-standing inefficiencies into the learned baseline: a site whose air conditioning has run continuously for months appears normal in its own history, so a regression model learns the inflated usage as expected consumption [6]. Third, energy consumption is meaningful only in context. A site may consume more energy because it is genuinely inefficient, but also because it is larger, carries more traffic, or hosts a more complex configuration [7, 8]; fixed thresholds and population-global outlier detection therefore conflate structural heterogeneity with inefficient operation.

This paper addresses these challenges by treating energy inefficiency as a peer-relative pattern: a site becomes a candidate for inspection when its energy behaviour is inconsistent with that of structurally comparable peers. We instantiate this idea through minimum-distortion embedding (MDE) [9], a general framework for learning low-dimensional representations from pairwise relationships. Our formulation embeds sites so that structural peers with consistent energy behaviour remain close, while an energy-aware repulsion term pushes sites with unusually high consumption away from their local peer groups. The resulting displacement provides an anomaly score that ranks sites for field investigation, and the ranking can further be distilled into lightweight supervised classifiers through pseudo-labels.

The main contributions of this paper are as follows.

  • We propose an energy-aware MDE formulation that integrates structural similarity and local energy deviation in a single push-pull distortion objective. To the best of our knowledge, this is the first application of distortion-based representation learning to site-level energy inefficiency detection in mobile networks.

  • We derive an embedding-relative displacement score that quantifies how far each site sits from its structural peer group, normalised by the intrinsic spread of that group, and we show how the score supports pseudo-label generation for downstream supervised models.

  • We construct a controlled evaluation environment grounded in operational data from 5,372 live mobile network sites, with group-specific baseline energy models and four realistic classes of injected inefficiency (overload, cooling overhead, idle-RF load, and

non-RAN parasitic load), enabling quantitative evaluation despite the absence of real inefficiency labels.

  • We present a comprehensive empirical study against unsupervised detectors, supervised residual-based methods, and a privileged physics reference across contamination rates from 1% to 99%, together with a representation-level analysis showing that the learned embedding itself improves standard detectors, and a teacher-student experiment demonstrating a practical deployment pathway.

To support reproducibility, the full implementation and experimental code are publicly available at [10].

The remainder of this paper is organised as follows. Section 2 reviews related work. Section 3 presents the proposed energy-aware embedding framework. Section 4 describes the controlled evaluation methodology, and Section 5 the experimental setup. Section 6 reports and discusses the results, and Section 7 concludes the paper.