arXiv:2608.30889eess.SYAug 2026

Manuscript Offprint

arXiv:2608.30889

Safety Screening for Voltage Control in Active Distribution Grids via Distributionally Robust Conformal Screening

Sarra Bouchkati, Petros Ellinas, Adriana Geisler, Steffen Kortmann, Johanna Vorwerk, Spyros Chatzivasiliadis, Andreas Ulbig

Sarra Bouchkati ∗,†^{*,\dagger}, Petros Ellinas ∗,†^{*,\dagger}, Adriana Geisler ∗,†^{*,\dagger}, Steffen Kortmann, Johanna Vorwerk, Spyros Chatzivasiliadis, and Andreas Ulbig

Abstract—Deploying a new control policy for voltage control in active distribution grids requires evidence that physical limits will be satisfied before the policy is tested on the physical grid. This assessment is difficult for two reasons. First, simulations cannot capture every disturbance, modeling error, and device interaction present in the real grid. Second, historical measurements reflect operation under existing control policies, whereas a new policy may drive the grid into different operating conditions. To address these challenges, we propose Distributionally Robust Conformal Safety Screening (DR-CSS), a policy-agnostic framework for pre-deployment, scenario-by-scenario screening of a new control policy using historical data and a nominal simulator. For each new scenario, the simulator predicts a future voltage trajectory for the whole grid; DR-CSS then constructs a conformal safety interval around this prediction using historical simulation-to-reality errors. The interval is further enlarged to account for closed-loop changes induced by the deployment of the new policy and its interactions with the remaining controllers. To the best of our knowledge, DR-CSS is the first framework in power systems to combine historical data from an existing control policy with an imperfect simulator for pre-deployment safety screening of a new policy. Experiments on the IEEE 33-bus and IEEE 141-bus systems evaluate the deployment of learning-based voltage control policies and show that DR-CSS identifies all unsafe test scenarios. To reduce unnecessary warnings on safe scenarios, we adapt the safety intervals to different operating conditions and gradually introduce new policies with recalibration after each stage. These extensions increase the informational value of the safety screening and support safer deployment decisions in active distribution grids.

Index Terms—Active distribution grids, conformal prediction, distribution shift, learning-based control, voltage control, voltage safety.

I. INTRODUCTION

One of the growing challenges in operating active distribution grids is maintaining bus voltages within permissible limits. Numerous inverter-interfaced distributed energy resources (DERs), flexible loads, and heterogeneous control devices operate as independent decision-making components, forming a complex multi-agent environment that shapes real-time grid operation. While the intermittency of renewable DERs increases the risk of voltage-limit violations [1], smart inverters can help regulate voltages through their fast and continuously adjustable reactive-power capabilities [2]. Coordinating reactive-power injections to maintain acceptable voltage profiles, often while limiting control effort or associated costs, is commonly referred to as the Volt-Var control problem. Various control policies, or automated decision-making rules, have been proposed to address this problem, ranging from simple rule-based local droop schemes to advanced learning-based methods such as reinforcement learning (RL) [3]–[7]. However, because these policies often act solely based on only partial grid information, they may fail to guarantee grid-wide safe voltage control due to the lack of coordination [8]. Several approaches aimed at addressing safety at the control policy-design stage. Safe RL techniques embed safety layers or constraint-satisfaction mechanisms directly into the training process to minimize operational risk, typically at the cost of more conservative exploration, or degraded nominal performance [4], [9], [10]. Crucially, these methods aim to enforce safety during policy training, but their guarantees are typically tied to the assumed training environment. They therefore do not guarantee grid-wide safety after deployment, where interactions with the physical grid and other controllers may lead to unanticipated voltage violations.

Deploying a new control policy at one or more inverters changes its interactions with the grid and with the controllers that remain in operation. Therefore, a key open problem is how to assess, before deployment, whether a new control policy introduced at one or more inverter buses will maintain all bus voltages within their admissible limits, using historical data and an imperfect simulator and without testing unsafe conditions on the physical system.

Ensuring the safe deployment of new control policies involves two complementary procedures: validation, which evaluates performance through simulation and empirical testing, and analytical verification, which provides analytical safety guarantees. Both are challenging in distribution grids because grid operators often lack a sufficiently accurate model of the physical system. In practice, distribution-grid models are limited by incomplete observability, data-quality issues, and imperfect topology knowledge [11], [12], as well as uncertainties in renewable injections, load behaviour, and measurement errors [13]. Traditional validation tools, such as scenario simulation and hardware-in-the-loop testing [14]–[16], therefore remain conditional on model fidelity and scenario representativeness. Direct testing of potentially unsafe conditions on the physical grid is also unacceptable, since power grids constitute a safety-critical infrastructure. Furthermore, historical operational data provides only limited support for evaluating

∗^{*}contributed equally to this work.

†^{\dagger}Corresponding authors: Sarra Bouchkati (e-mail: s.bouchkati@iaew.rwth-aachen.de), Petros Ellinas (e-mail: petrel@dtu.dk), and Adriana Geisler (e-mail: a.geisler@iaew.rwth-aachen.de).

Sarra Bouchkati, Adriana Geisler, Steffen Kortmann, and Andreas Ulbig are with IAEW at RWTH Aachen University, Aachen, Germany.

Petros Ellinas, Johanna Vorwerk, and Spyros Chatzivasiliadis are with the Department of Wind and Energy Systems, Technical University of Denmark, Kongens Lyngby, Denmark.

The work of P. Ellinas and S. Chatzivasileiadis is supported by the European Research Council (ERC) Starting Grant VeriPhIED, Grant Agreement No. 949899.

new control policies, since it is generated under the closed-loop behavior of previously deployed policies. Consequently, it may not adequately represent the states, interactions, and control actions that would arise after an untested control policy is introduced.

Analytical verification workflows share a common modeling bottleneck: their guarantees are only as reliable as the models on which they are built. Formal verification, reachability analysis, and certificate-based methods can provide strong deterministic guarantees under suitable assumptions, but they typically require accurate system models, tractable mathematical abstractions, and substantial computational resources [17]−[20][17]-[20]. When the underlying model deviates from the true system, these guarantees no longer transfer to physical deployment.

Statistical uncertainty quantification offers a complementary way to assess new control policies before deployment. Existing approaches include probabilistic voltage-risk assessment and conformal prediction for power-system forecasts and voltage trajectories [21]–[24]. Conformal prediction is attractive because it uses past differences between predictions and observations to construct uncertainty intervals without assuming a specific probability distribution. However, these intervals remain reliable only when past observations are representative of the setting being assessed. This condition may fail after a new control policy is deployed at one or more inverters because this new policy can produce different closed-loop grid behaviour through its interactions with the grid and the remaining controllers. Consequently, uncertainty intervals calibrated under the pre-existing control policy may not remain valid after deploying a new policy.

This is an off-policy conformal prediction setting, in which data collected under the existing control policies are used to assess a new one before deployment. Although off-policy conformal methods have been studied in reinforcement-learning and multi-agent applications [25], [26], to the best of our knowledge, this work is the first in the power-systems literature to formulate control policy replacement as an off-policy conformal problem for grid-wide voltage-safety screening.

We propose Distributionally Robust Conformal Safety Screening (DR-CSS), a policy-agnostic statistical framework for pre-deployment, scenario-by-scenario screening of a new control policy using historical data and an imperfect nominal simulator. DR-CSS complements existing validation and verification tools and can be applied to predictions produced by power-flow simulators, reduced-order models, learned surrogates, or verification workflows. For each operating scenario, the nominal simulator produces a future voltage trajectory, around which DR-CSS constructs an uncertainty interval using historical simulation-to-reality errors. The interval is then enlarged to account for bounded changes in prediction-error behaviour after a new control policy is deployed at one or several inverters.

We further extend DR-CSS in two practical ways. First, context-aware calibration adapts the uncertainty intervals to different operating conditions, so that one overly conservative interval is not used for every scenario. Second, gradual policy change introduces the new control policy in stages and recalibrates DR-CSS after each stage, reducing the change that must be handled if several inverters get a new control policy at once.

In summary, the main contributions are:

• We introduce, to the best of our knowledge, the first framework in power systems for pre-deployment, scenario-by-scenario screening of a new control policy. Distributionally Robust Conformal Safety Screening (DR-CSS) is model-agnostic and thus can be applied to any black-box control policy.

• We extend DR-CSS with context-aware calibration, which adapts the uncertainty intervals to different operating conditions, and gradual control policyreplacement, which updates the screening method after each deployment stage.

• Employing the IEEE 33-bus and 141-bus cases, we demonstrate how DR-CSS reaches the target statistical coverage with finite and informative uncertainty intervals, reduces the intervals’ average width by up to 69%, and flags every unsafe voltage trajectory in the gradual-deployment experiment.

The remainder of the paper is organized as follows. Section II formulates the voltage-control and deployment-assessment problem. Section III presents DR-CSS. Section IV reports the numerical results. Finally, Section V concludes the paper and outlines future work directions.

References (28)