Manuscript Offprint

arXiv:2611.03849

LaplaceDiag: Fault Diagnosis through Changes in Learned Actuator Effects

Oliver Niggemann

Abstract

Identifying faulty components from sensor anomalies is difficult because fault effects can propagate through a plant and different faults can produce similar observations. Detailed component models and labeled fault examples may also be unavailable. We introduce LaplaceDiag, a data-driven method that uses changes in actuator effects to narrow the search for faulty equipment. Actuators act on specific devices and mechanisms, so their changed effects can provide clues to root causes. LaplaceDiag learns a healthy plant model with LaplaceNet, a neural network that operates in Laplace space. It separates nonlinear prediction based on measured history from an explicit matrix that describes how actuator values affect sensor values. Keeping the history predictor fixed allows current actuator effects to be estimated by linear regression without retraining the neural network. Comparison with a healthy reference accounts for estimation uncertainty and normal variation to detect changes and generate actuator-related diagnostic hypotheses. The method supports online and offline diagnosis, providing an intermediate step between anomaly detection and identifying faulty components. We successfully evaluate LaplaceDiag on two datasets.

Keywords: Fault diagnosis, system identification, neural networks, actuator monitoring, uncertainty quantification.

1 Introduction

Anomaly detection asks whether a system behaves differently from healthy operation. Diagnosis seeks the faulty components that explain this behavior. These may be sensors, valves, pumps, or other parts of the plant. Model-based diagnosis uses process relationships to distinguish possible faults, while supervised classifiers learn fault classes from labeled examples (Isermann 2005, Zhou et al. 2025).

Locating a faulty component is difficult because its effects can appear in measurements elsewhere in the plant. Different faults can also produce similar observations. Detailed component models or representative fault examples may be unavailable. We therefore pursue a more limited goal: use healthy recordings to narrow which equipment should be investigated.

Actuators can have a direct mechanical connection to identifiable equipment. An electric motor moves an aircraft valve flap through gears and a lever (Isermann 2005). A pneumatic actuator moves a control-valve stem to regulate flow (Bartyś et al. 2006). These connections motivate an intermediate step between anomaly detection and component diagnosis: use changes in actuator effects as clues to faulty components.

Here, an actuator effect is the modeled relationship between actuator values and subsequent sensor values. LaplaceDiag uses LaplaceNet, a specialized neural network learned from healthy actuator and sensor recordings, to model this relationship.

LaplaceNet encodes earlier measurements into a learned state representation. Predicted sensor values combine the continuation of past operation, computed from this state, with a separate contribution from later actuator values (Zimmering et al. 2026). For the modeled linear actuator response, the Laplace transform replaces accumulation over time by multiplication with a transfer function. After transforming back, this contribution is GNNUG_{\mathrm{NN}}U: UU collects actuator values over the prediction interval, and GNNG_{\mathrm{NN}} is the neural model's matrix mapping them to additional sensor values. The learned state need not coincide with physical state variables.

LaplaceNet jointly learns its history predictor and the actuator-effect matrix GNNG_{\mathrm{NN}}. For diagnosis, we keep the history predictor fixed and fit actuator effects by linear least squares on separate healthy recordings. This gives the healthy diagnostic reference G0G^0. It need not equal GNNG_{\mathrm{NN}}, because the data and fitting procedures differ. For a block ending at timestep tt, the same linear estimator gives the current matrix G^t\widehat{G}_t. Diagnosis compares G^t\widehat{G}_t with G0G^0, so both sides use the same estimation procedure. This extra fit introduces no physical knowledge beyond the learned actuator-to-sensor relationship. The network and G0G^0 remain fixed. Uncertainty and healthy calibration determine which changes are supported.

We propose LaplaceDiag, a new algorithm that detects actuator-effect changes and uses them to support component diagnosis, online or offline. We ask:

  1. RQ1. Can LaplaceDiag detect sustained actuator-effect anomalies? We compare de-tection and healthy false alarms with baselines under the same calibration target.

  2. RQ2. What conditions make actuator-effect estimates informative? We examine whether actuator variation distinguishes their effects and how model error limits interpretation. Uncertainty helps decide when the evidence is insufficient.

  3. RQ3. Do detected actuator-effect changes help locate faulty components? We test whether the indicated actuator or connected mechanism matches the known fault and compare ambiguity with projection baselines. Fault labels are used only for evaluation.

Our contribution is a diagnosis procedure that compares explicitly estimated LaplaceNet actuator effects with a fixed healthy reference and calibrates repeated checks. It retains uncertainty and insufficient-information outcomes. Affine neural prediction and parameter-change diagnosis are established (Masti et al. 2020, Isermann 2005). We test whether this specific combination improves actuator attribution over same-model and independent neural projections.

Section 2 positions the method, Section 3 explains it, and Section 4 presents the distinct comparisons and limits.

References (20)