LLM-PowerTrace: A Dataset of Time-Resolved GPU Power Traces for AI Compute

Jiansheng Wang, Jaskeerat Singh, Haochen Xu, Xinyi Li, Mingyuan Yan, Shaohui Liu, Yuzhuo Li, Yize Chen, Wenqi Cui

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

ABSTRACT

AI compute is becoming large and fast-changing electrical loads. Its impacts on data center infrastructure and power grids depend not only on total energy consumption, but also on how their power draw moves over sub-second to minute timescales, including peaks, ramps, and synchronized fluctuations across accelerators. Existing energy benchmarks for large language models (LLMs) report aggregate quantities such as joules per token and rarely release the underlying time-series measurements, leaving these power dynamics poorly characterized and difficult to model. We introduce LLM-POWERTRACE, an open dataset of time-resolved, per-GPU power traces for LLM fine-tuning and inference, sampled every 100 ms on varying NVIDIA platforms paired with complete workload and system metadata. For fine-tuning, LLM-POWERTRACE profiles open model families spanning a wide range of model sizes and fine-tuning methods, together with controlled sweeps over batch size, sequence length, precision, parallelism, and checkpointing. For inference, it covers variations in concurrency, GPU frequency, KV-cache and weight quantization, prompt and output lengths, and request-arrival patterns. Built upon power traces, we define power-grid-facing metrics as well as AI-compute power&energy scaling law for extrapolating beyond the measured settings. Together, LLM-POWERTRACE provides a dataset foundation for modeling, forecasting, and managing the fast-changing electrical behavior of AI compute¹.

1 INTRODUCTION

AI data centers are among the fastest-growing sources of electricity demand (Shehabi et al., 2024; International Energy Agency, 2025). Beyond their substantial energy consumption, their electrical behavior is shaped by the tightly coordinated execution of AI workloads. Modern AI clusters can synchronously shift thousands of accelerators among compute-bound, memory-bound, communication-bound, and idle states, producing rapid and possibly structured variations in power demand. These dynamics are already becoming operationally significant, where large-scale training jobs can generate synchronized power swings that require mitigation through software, hardware, and energy-storage mechanisms (Choukse et al., 2025), while LLM workloads can induce irregular power transients impacting power grids (Li et al., 2024). For instance, in July 2024, approximately 1,500 MW of data center load in Northern Virginia was abruptly disconnected almost simultaneously following a single transmission-system fault (North American Electric Reliability Corporation, 2025). As power availability increasingly constrains the expansion and operation of AI data centers, understanding the magnitude, variability, and temporal structure of AI power demand is essential for both data center operation and energy systems planning.

*Equal contribution; jw9461@nyu.edu, jaskeer1@ualberta.ca, hx2493@nyu.edu †Equal advising; yize.chen@ualberta.ca, wenqicui@nyu.edu ¹Code and dataset are available at https://systems-power-review.github.io/training-power-trace-explorer/

Table 1: Comparison with related resources. “Power series”: time-resolved power traces are released. “Controlled”: runs form controlled configuration sweeps.

ResourceTrainInferPower seriesPer-GPUControlledResolution
Words to Watts (Samsi et al., 2023)X✓XX✓aggregate
ML.ENERGY (Chung et al., 2025)X✓XX✓aggregate
BurstGPT (Wang et al., 2025)X✓XXXrequest log
MIT Supercloud (Samsi et al., 2021)✓✓✓✓X100 ms
LLM-POWERTRACE (ours)✓✓✓✓✓100 ms

Existing characterizations of AI power and energy use remain predominantly energy-centric (Chung et al., 2025; Oviedo et al., 2026). However, grid operators, data center owners, and AI servers are concerned not only about overall bulk energy or tokens per joule, but also about when power is drawn and how fast it changes. A workload with low total energy consumption can still create operational challenges through high power peaks, steep ramps, or unregulated fluctuations. Such power dynamics can impose additional operational requirements both on data center electrical infrastructure such as feeders, transformers, power distribution and backup units, as well as on power systems such as frequency regulation, ramping capability, and other balancing resources (Chen et al., 2025).

Yet the data needed to study AI compute’s power and energy dynamics remain limited. Benchmarks commonly report total energy consumption, energy per token, query, or run (Samsi et al., 2023; Luccioni et al., 2024; Chung et al., 2025; Fernandez et al., 2025; Tschand et al., 2025). LLM serving datasets capture request arrivals and workload statistics but not corresponding power measurements (Wang et al., 2025), while cluster telemetry datasets are not organized around controlled, configuration-labeled LLM workloads (Samsi et al., 2021). As a result, researchers seeking to characterize (Maliakel et al., 2026), model and scale (Hoffmann et al., 2022), forecast, or control AI power dynamics (Colangelo et al., 2026) lack open data that directly links workload configurations and execution events to high-resolution power trajectories.

To address this gap, we introduce LLM-POWERTRACE to connect time-resolved GPU power measurements with fine-tuning and inference workload characteristics, execution configurations, and hardware properties. It contains 1788 fine-tuning runs and 405 full serving runs on variations of NVIDIA GPU platforms and datasets, each with 100 ms per-GPU telemetry, the full run configuration, and timestamped execution events. Our contributions are threefold. First, LLM-POWERTRACE provides a systematic, configuration-labeled collection of high-resolution power traces for both LLM fine-tuning and inference, enabling characterization of rich power behaviors beyond aggregate or average energy metrics. Second, building on these traces, we define grid-relevant metrics and demonstrate both model-based analysis and empirical scaling laws for identifying key factors and extrapolating power and energy behaviors beyond the measured configurations. Third, we release the data, metric-computation code, and an interactive explorer, together with validation pipeline that supports reviewed community extensions of the dataset.

References (34)