Adversarial Process Disturbances at a Deployable Alarm Budget: Detector Evaluation on a Simulator and a Real Plant

Benjamin Blakely

Benjamin Blakely, Senior Member, IEEE

Abstract—Industrial anomaly detection is evaluated largely on simulators, and recent work reports large drops, with unstable rankings, on real plant data. We ask whether that extends to the security case. We evaluate eleven detectors across classical, neural, dependency and causal families on a simulated chemical process and a sodium thermal-hydraulic facility: different processes sharing no equipment, but both continuous, at steady state, and perturbed only through temperature, pressure, flow and valve, never composition. Three conditions prior work does not cover: disturbances authored against a threat model rather than native faults; one construction applied to both processes; and detection read at a declared false-alarm budget. The drop persists throughout. The simulator panel looks deployable, neural matching classical; on plant telemetry detection collapses and the neural family trails, a gap that in-sample thresholds likely understate. Which detector wins transfers between the two processes; how often it fires does not. Two results hold on both. Sequential valve manipulation defeats the whole panel: at tier 2 no detector flags more than 0.17 of its perturbed samples, against 0.89 or better for most disturbances. And the plant's collapse is not merely that its disturbances are weaker, though they are by about twelvefold; matched on measured strength, the plant is never the better detected.

Index Terms—Anomaly detection, industrial control systems, operational technology, evaluation methodology, process monitoring.

I. INTRODUCTION †^{\dagger}

Cybersecurity anomaly detection for operational technology has largely inherited its methods, and its evaluation habits, from information technology. That inheritance has costs which the literature documents rather than disputes: regulatory qualification burden in safety-critical settings [1], [2], inference cost on embedded control hardware [3], [4], the scarcity of labeled incident data [4]–[6], and degradation when a model meets a process other than the one it was fitted to, which obliges the operator to retrain and requalify it there [7]–[11].

Those costs would pay for themselves if the added capacity bought detection performance where the detector is deployed. The difficulty is that most of the evidence that it does is produced somewhere the detector is not deployed. Simulators and public benchmarks dominate the evaluation literature, and the field already documents their weaknesses [5], [9], [12]–[14], while the relative ranking of methods is known to shift with the dataset [8], [9], [11].

The concern is not a new one: the simulated-to-real gap in industrial anomaly detection is an established result, benchmarked across thirty methods and three processes by Hartung et al. and described below [9], [15].

What is not established is whether it survives the conditions a security evaluation imposes. Three differences matter. First, the prior result uses each process's own process faults; an adversary is not a fault, and a disturbance constructed to stay inside a plant's admissible envelope is a different object from a valve sticking. Second, comparing one process's faults against another's leaves the disturbance and the telemetry varying together; applying one construction to both removes the disturbance design as a variable, though not the realized magnitudes, which each process's own envelope sets. Third, performance was assessed with F1 and area under the precision-recall curve, which aggregate over thresholds an operator would never select.

We therefore ask a narrower question than the prior work answered: does the transfer failure persist for adversarial disturbances, under an identical disturbance construction, at a false-alarm rate a control room could staff? 1^{1} It does. A second question follows from it, and the two are separable: whether the detector ranking that holds under a threshold-free metric still holds at a budget an operator would actually choose.

A companion technical report covers the corpus construction and the single-process results in more detail than is reproduced here [18].

Our contributions are four:

  1. A tiered, physics-admissible disturbance framework with declared per-channel bounds, portable across process data models, which lets the same adversary model be

This work has been submitted to the IEEE for possible publication. Copyright may be transferred without notice, after which this version may no longer be accessible.

B. Blakely is with Argonne National Laboratory, Lemont, IL 60439 USA (e-mail: bblakely@anl.gov).

This work was funded by the U.S. Department of Energy, Office of Nuclear Energy, Advanced Reactor Safeguards and Security program, and was partially supported by the U.S. Department of Energy, Office of Science under DOE contract number DE-AC02-06CH11357. The submitted manuscript has been created in part by UChicago Argonne, LLC, operator of Argonne National Laboratory. Argonne, a DOE Office of Science laboratory, is operated under Contract No. DE-AC02-06CH11357. The U.S. Government retains for itself, and others acting on its behalf, a paid-up nonexclusive, irrevocable worldwide license in said article to reproduce, prepare derivative works, distribute copies to the public, and perform publicly and display publicly, by or on behalf of the Government.

†^{\dagger}AI-assisted content, in this and every section marked †\dagger; see the Acknowledgment [36]–[42].

1^{1}Adversarial here means attacker-authored within an admissibility envelope, not optimized against a deployed detector: an adversary who queries the detector or maximizes impact beneath its threshold [16], [17] is a stronger one than we instantiate, and Section VIII says so.

instantiated on two processes that share no equipment (Section IV).

  1. Confirmation that the simulated-to-real transfer failure [9] extends to adversarial disturbances, under one disturbance construction applied to both processes rather than each process's own faults (Section VI).

  2. A separation between two things often reported together: the detector ranking transfers across the two processes, positively at every operating point examined, while the absolute detection rate does not (Section VI).

  3. A disturbance no detector flags reliably per sample, on either process. At tier 2 none flags more than 0.17 of sequential valve manipulation's perturbed samples, 0.10 on the plant and 0.17 on the simulator, where most disturbances have a detector at or above 0.89. Because it holds on both, it does not depend on either process being representative (Section VI). Read per episode rather than per sample the same cell reports alarms in 196 of 204, which is why the granularity has to be stated rather than assumed.