arXiv:2610.33401cs.CROct 2026

Manuscript Offprint

arXiv:2610.33401

From Caveman to COBA: Coordinated Optimization-Based Attacks on Grid-Edge Smart Inverters in DER-Rich Power Systems

Emad Abukhousa, Anna Raymaker, Animesh Chhotaray, Daniel Molzahn, Saman Zonouz, Sakis Meliopoulos

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

Emad Abukhousa, Anna Raymaker, Animesh Chhotaray, Daniel Molzahn, Saman Zonouz, Sakis Meliopoulos

School of Electrical and Computer Engineering, Georgia Institute of Technology, Atlanta, GA, USA

{emadak, araymaker3, achhotaray3, molzahn, szonouz6, sakis.m}@gatech.edu

Abstract—Aggregation platforms and smart-inverter control channels can allow a compromised coordination layer to alter active- and reactive-power commands across a geographically distributed DER fleet. This paper introduces the Coordinated Optimization-Based Attack (COBA), which uses network information and location-specific DER P/Q setpoints to maximize thermal loading on a selected transmission corridor. COBA is compared with low-information CAVEMAN baselines limited to a single uniform fleet command: all-off, all-on, maximum reactive absorption, or maximum reactive injection. The Hawaii Synthetic Grid–37 Buses case is evaluated with rooftop-photovoltaic-like capability aggregated at 20 selected 69-kV buses and verified using MATPOWER power flow. Under the case's single-reference-bus balancing convention, COBA overloads B86 (WAIALUA69–WAIANAE69) near 30% penetration and B51 (COCONUT69–PALM69) near 55%, while same-target uniform loadings remain lower and uniform commands primarily stress other natural weak lines. The results show that topology, target selection, and command capability determine DER-induced thermal risk beyond aggregate penetration alone.

Index Terms—Cyber-physical security, distributed energy resources, smart inverters, power flow, adversarial optimization.

I. INTRODUCTION

Distributed energy resources (DERs) connected through smart inverters are extending distribution-level control actions into the operational boundary of the bulk power system. Aggregators, vendor clouds, and fleet-management platforms can coordinate active-power management and reactive-power support across many devices. Compromise of such a coordination layer can convert cyber access into geographically distributed physical actuation. IEEE Std. 1547-2018 defines DER interconnection and interoperability requirements, while IEEE Std. 1547.3-2023 provides cybersecurity guidance for DER interconnections [1], [2]. NERC and the U.S. Department of Energy identify DER aggregation and associated control surfaces as emerging bulk-system reliability and security concerns [3], [4].

Prior work identifies three relevant attack classes. Load-altering attacks, BlackIoT, and MaDIoT demonstrate that coordinated access to grid-connected devices can create bulk-system consequences and that timing and geographic selection matter [5]–[7]. However, these studies primarily manipulate demand rather than inverter P/Q setpoints. False-data-injection and load-redistribution attacks use network knowledge to influence state estimation or operator decisions [8], [9]. The attack considered in this paper instead directly actuates DER commands. Smart-inverter studies and the SUN:DOWN disclosure show that inverter, monitoring, and cloud control paths can expose active- and reactive-power functions [10]–[12]. Reactive-power manipulation has also been linked to voltage and protection effects at individual prosumer sites [13]. While these results establish a credible command-injection surface, they leave a critical gap: existing work does not quantify when a fixed compromised DER fleet can be coordinated to redirect thermal stress toward a selected transmission corridor.

The key question is how a fixed compromised DER fleet can be coordinated through network-aware, location-specific commands to maximize loading on a selected transmission corridor. Uniform all-on, all-off, and all-reactive commands serve as low-information baselines that reveal corridors naturally sensitive to fleet-wide disturbances, but they do not determine whether the same fleet can make the selected corridor limiting. This defines the screening problem: holding the DER fleet, penetration definition, selected corridor, and AC verification procedure fixed while varying attacker information and command capability.

This paper presents two attacks, the Coordinated Optimization-Based Attack (COBA) and CAVEMAN, as adversarial approaches to the DER-screening problem. CAVEMAN represents a low-information attacker limited to one uniform fleet command, whereas COBA represents a network-aware attacker that selects location-specific P/Q setpoints using topology, branch ratings, DER locations, capability limits, and an operating point. The comparison determines whether COBA can overload the selected corridor at a lower penetration than under uniform commands or when no uniform command reaches its thermal rating within the evaluated range. This study makes two contributions. First, it formulates a common AC screening framework that compares low-information uniform DER commands with network-aware, location-specific P/Q coordination under the same compromised fleet, penetration definition, target corridor, and verification procedure. Second, it applies the framework to the Hawaii Synthetic Grid–37 Buses case to quantify first-overload thresholds and distinguish naturally stressed corridors from corridors made limiting through coordinated commands.

II. THREAT MODEL AND SCREENING PROBLEM