arXiv:2610.30182cs.CROct 2026

Manuscript Offprint

arXiv:2610.30182

Detecting AI Training in Datacentre Power

Tom Kimpson, Mauricio Baker, Emlyn Graham

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

Abstract

AI governance agreements require methods to detect large model training runs on a monitored computing cluster, without trusting the operator. We develop a method to detect synchronous model training in facility-level power by Viterbi tracking of the wandering iteration cadence. On simulated datacentre power, when the operator makes no attempt to hide, the Viterbi tracker detects at least 96% of training runs against a declared inference workload, at a 1% false-alarm rate and within 0.04 of the Neyman–Pearson optimum, given a meter that samples at 2 Hz or faster. Of eight adversarial strategies an operator might use to hide, only extreme variation of the work per iteration evades the tracker. Its strongest form hides training in up to 73% of five-minute observations, but over a day at least 87% of such runs are still caught, at a 0.1% false-alarm rate per run. This adversarial strategy costs no throughput, but in small-scale training the operator needs 93–267% more compute to reach the same loss. A modest passive meter is sufficient to make hidden training both detectable and expensive, which makes power metering a promising part of compute verification that does not depend on trusting the operator.

1. Introduction

AI governance agreements will require regulating training runs (Shavit, 2023; Sastry et al., 2024; Baker et al., 2025; Heim & Koessler, 2024). This necessitates an external verifier to identify when training is occurring on a monitored cluster, against an operator who is trying to hide their training. There are multiple channels that could provide the verifier with diagnostic information to identify hidden training. These include on-chip mechanisms that log activities for later analysis (Shavit, 2023; O'Gara et al., 2025), network taps that monitor data exchanged between chips, or human-centred approaches such as whistleblower programs or interviews of operator personnel (Baker et al., 2025). However, each of these channels requires trusting either hardware that is under the control of the operator, or the operator personnel themselves. Conversely, off-chip sensors that take analog, physical measurements of the cluster (e.g. power or electromagnetic emissions) do not require trusting the operator. Such sensors could be retrofitted to existing datacentres (e.g. clamping a power meter on an input cable) and secured against tampering by the operator.

AI training has already been shown to leave a signature in the power drawn by the hardware that can serve as a diagnostic to identify and separate training from inference. A 10 MHz current probe clamped around the GPU’s PCIe power supply cables can separate training from inference and from non-AI work at 97% accuracy (Gargiulo & Kulp, 2026), a result robust against many but not all adversarial strategies. On-chip 1 Hz telemetry counters that measure power (among other telemetry: utilisation, memory, etc.) can identify training at 98.2% accuracy, falling to 43–87% against the hardest workloads when they are adversarially disguised (Rahman & Tajdari, 2026). In practice, any realistic AI governance agreements that use off-chip sensors will rarely have such fine-grained access to the GPU hardware. Power meters that can be retrofitted to existing facilities and secured against tampering are likely to sit at the level of the rack or facility input, with sampling frequencies ∼\sim10 Hz (i.e. six orders of magnitude slower than the board probe) and behind a power-delivery path that low-passes and dilutes the signal. At this level the training signal is still visible, and large enough that datacentre and grid operators treat it as an engineering control problem (Patel et al., 2023; Ko & Zhu, 2025).

At the facility meter, the signature of training is its iteration cadence. Each iteration alternates a high-power compute phase with a low-power communication phase, about once a second, and this cycle puts a narrow line in the power spectrum. Detecting that line at a facility meter is harder than at the board, for two reasons. First, the cadence of a real run is not fixed. Stragglers, degraded hardware and temperature change the iteration time over seconds to hours (Section 2.1), so the spectral line wanders, and a test that

1^{1}School of Mathematics and Statistics, The University of Melbourne, Parkville, VIC 3010, Australia 2^{2}Machine Alignment, Transparency & Security (MATS) 3^{3}Department of Engineering Science, University of Oxford, Oxford, UK. Correspondence to: Tom Kimpson tom.kimpson@unimelb.edu.au.

Preprint. October 23, 2026.

looks for a sharp peak at one frequency loses it. Second, an operator who wants to hide can make the line wander on purpose, or smear it away, by inserting idle time between iterations or by varying the work done in each. Hiding is not free, however. A training operator cannot reshape its signal freely; every distortion of the schedule costs throughput, learning efficiency, or both. The question is therefore not whether training can be hidden, but whether it can be hidden cheaply.

In this paper we develop a method to detect training in facility-level power measurements against an operator who is trying to hide it, and we measure what hiding costs. We model the power of a datacentre running training and inference (Section 2) and pass it through a model of an off-chip meter (Section 3). To follow the wandering line we borrow a Viterbi line tracker from passive sonar and continuous-gravitational-wave searches (Section 4). Against an operator who does not hide, the tracker detects training in almost every five-minute window, within 0.04 of an optimal ceiling, while fixed-frequency tests fail once the cadence drifts (Section 5). It needs only a meter that samples at 2 Hz or faster and averages over no more than 0.5 s. We then test eight ways for an operator to hide (Section 6). Fixed-frequency tests are defeated cheaply: varying the work per iteration hides 88% of windows at no cost in throughput. The tracker is defeated only by extreme work variation, and that has a cost in learning instead: in small-scale training, the operator needs 93–267% more compute to reach the same loss. Over a day of observation, the strongest strategy we found escapes detection in 13% of runs, at a run-level false-alarm rate of 0.1% (Section 7.1).

Our main conclusion is that a passive power meter outside the operator’s control can detect synchronous training, and that hiding from it is expensive. Two limits apply. The meter detects a periodic schedule, not training itself, so non-training loads with a training-like cycle also trip it (Section 7.2). And our evidence is synthetic: the traces come from a model, not from a measured multi-GPU facility (Section 7.3).

This paper is organised as follows. Section 2 gives the model of datacentre training and inference power that generates every trace below, and Section 3 fixes what the verifier sees through an off-chip meter and what a concealing operator may do to hide from it. Section 4 develops the detector, a Viterbi line tracker; Section 5 reports its power against the inference null and the minimum meter it needs; and Section 6 prices what it costs a concealing operator to defeat it. Section 7 asks how likely a concealing operator is to be detected over a run, covers the non-training loads that imitate training, and sets out the limitations. Section 8 concludes.

References (43)