arXiv:2610.30551cs.NIOct 2026

Manuscript Offprint

arXiv:2610.30551

OMRC: Multipath Reliability for Direct-Connect Optical Interconnects

Eric Ding, Keshav Pradeep, Rachee Singh

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

Eric Ding, 1,∗^{1,*} Keshav Pradeep, 1^{1} and Rachee Singh 1^{1}

1^{1}Department of Computer Science, Cornell University, 107 Hoy Rd, Ithaca, NY 14853, USA

*ericding@cs.cornell.edu

Abstract: Network failures degrade Multipath Reliable Connection (MRC) in direct-connect optical datacenters. We propose Optical MRC (OMRC), which remaps collectives and circuits, preserving 95.7% of training throughput, restoring stalled inference, and achieving 4.7×4.7 \times MRC's simulated bandwidth.

1. Introduction

Distributed training and inference jobs exchange data among hundreds of accelerators through collective communication operations like ALLREDUCE and ALLTOALL. Even a single failed network link between two accelerators stalls the collective and the training or inference step that waits on the collective. Unfortunately, link failures occur frequently in production AI clusters due to link flaps, network interface card (NIC) and switch faults, and laser failures [1]. While the ML application can recover from such failures by restarting its processes on a new set of accelerators and rebuilding inter-accelerator connections, such a restart is expensive at scale.

Electrical vs. optical DC

Figure

Electrical DC. Ports connect to packet-switched planes.

Limitation 1

different ring orders

Topology and failure

Figure

Planes 0 and 1 order the GPUs 0,1,2,3 and 0,2,1,3. Link 0–1 fails in plane 0.

MRC

Figure

Since the ring keeps order 0,1,2,3, the send 0→10 \rightarrow 1 detours through GPU 2.

OMRC (this work)

Figure

OMRC moves the channel to plane 1 with order 0,2,1,3. Each send takes one hop.

Figure

Direct-connect optical DC. Ports connect to OCSes. Each OCS forms one ring, called a plane.

Limitation 2

switch failure

(a)

Figure

TP: three planes per pair; DP: one. A switch failure breaks both 0–2 and 1–3.

failed link

plane 0 / DP plane

Figure

Both DP pairs lose their only plane. MRC cannot use the TP planes.

plane 1 / moved plane

(b)

Figure

The OCS reallocates one plane from each TP pair to restore both DP pairs.

TP plane

Transfer

Fig. 1. (a) Electrical and direct-connect optical datacenters (DCs). NIC ports connect to packet-switched planes in an electrical DC and to optical circuit switches (OCSes) in a direct-connect optical DC. (b) Link and switch failures in a direct-connect optical DC. Each row shows a limitation of Multipath Reliable Connection (MRC) on direct-connect optical DCs and how OMRC addresses it. A channel is a slice of a collective that follows its own ring order. TP and DP denote tensor-parallel and data-parallel groups.

Hyperscalers avoid job restarts by handling link failures in the network transport with Multipath Reliable Connection (MRC) [1]. MRC runs on a multi-plane network in which the NIC of each accelerator splits its bandwidth across several lower-speed ports (Fig. 1(a), top). For example, an 800 Gb/s NIC operates as eight 100 Gb/s ports [1], each connected to a different plane. A plane is an independent packet-switched network, typically a two-tier Clos, that connects one port of each NIC in the cluster. Since all planes have the same structure, a path between two accelerators has the same length in every plane. MRC sprays the packets of a connection between two accelerators across the planes. When one path fails, MRC stops sending on that path and moves its traffic to the remaining paths. By design, the remaining paths have the same length as the failed path, so the connection loses only the failed path's bandwidth.

Since electrical packet switches in large ML datacenters (DCs) consume massive amounts of energy, recent work has proposed replacing them with optical circuit switches (OCSes) to achieve orders-of-magnitude efficiency gains [2]. In the resulting direct-connect datacenters, OCSes connect accelerator NICs with optical circuits, without any packet switches in between (Fig. 1(a), bottom). To maximize collective performance, network operators configure each OCS to connect two NIC ports of each accelerator into a ring, called a plane [2, 3]. Therefore, an accelerator with degree D (D NIC ports) belongs to D/2 planes. Ring collectives like ALLREDUCE run on all planes in parallel. Each step of a ring collective sends data to a neighbor in one hop within individual planes. Operators order the accelerators differently in different planes. With different orders, each accelerator has more neighbors and shorter paths to the other accelerators, which benefits traffic like ALLTOALL. In Fig. 1(b), each GPU has degree four and belongs to two planes (plane 0 orders the GPUs 0,1,2,3 and plane 1 orders them 0,2,1,3). Each communication group, the set of accelerators that communicate for one type of parallelism, has a dedicated subset of the planes [4]. For example, data-parallel (DP) and tensor-parallel (TP) groups use separate planes.

In this work, we show that, when applied to direct-connect optical datacenters, MRC reroutes around failed links with two important limitations. First, the planes of a direct-connect DC do not offer equal-length paths between a pair of GPUs. Two GPUs that are neighbors in one plane can be several hops apart in another plane. If link 0–1 fails in plane 0, MRC forwards its traffic through GPU 2 in plane 1 (Fig. 1(b), top row). This detour consumes the bandwidth of an extra link and adds latency. Second, a group that loses all of its planes stalls with MRC (e.g., due to switch failures), even when other groups have healthy planes (Fig. 1(b), bottom row).

We propose Optical Multipath Reliable Connection (OMRC), a control layer that extends the MRC transport for direct-connect optical DCs. When a link fails, OMRC remaps collectives onto intact planes (Fig. 1(b), top right). If a group loses connectivity, OMRC moves planes between communication groups by reconfiguring the topology (Fig. 1(b), bottom right). We implemented OMRC in MSCCL++ and evaluated it with training and inference jobs of Qwen1.5-MoE, a 14.3B-parameter mixture-of-experts (MoE) model, on four NVIDIA L40 GPUs connected through a Polatis OCS. When one link fails for 40 s during training, OMRC remaps the affected channel and improves training throughput by 5.3% over MRC. When the job loses its sole TP plane during inference, MRC stalls. OMRC moves one plane from the key-value (KV) cache transfer group to restore TP group connectivity, retaining 99.3% of pre-failure inference throughput. Large-scale simulations show that OMRC achieves up to 4.74×4.74 \times MRC's algorithmic bandwidth in networks with multiple failures.