arXiv:2610.11236cs.LGOct 2026

Manuscript Offprint

arXiv:2610.11236

Low-Cost Sensor Calibration for Indoor Air Quality Monitoring: A Dataset, Evaluation Scenarios, and a Lightweight Model

Jinyong Yun, Seokho Ahn, Hyungjin Kim, Sungbok Shin, Young-Duk Seo

Abstract

Low-cost sensors enable scalable indoor air quality monitoring but require calibration because of nonlinear distortions, noise, and temporal drift. The conventional strict pairwise calibration setting requires a co-located reference sensor at each deployment location and does not account for spatial and temporal heterogeneity. To address these limitations, we introduce a six-month dataset comprising multivariate indoor air-quality measurements from low-cost and reference sensors with contextual metadata collected at five locations. Using this dataset, we define four evaluation scenarios. The reference-efficient and location-transfer scenarios evaluate spatial generalization, whereas the long-term drift and event-conditioned scenarios assess robustness to gradual and abrupt distribution shifts. Based on these scenarios, we derive design requirements and propose a lightweight temporal model that combines input-window compression with residual temporal and feature fusion. Experiments show strong calibration performance across all four scenarios with low edge-inference cost.

1 Introduction

People spend about 90% of their time indoors, making indoor environments a major source of daily pollutant exposure and an important factor in human health (Jiang et al. 2011; Zhong, Lalanne, and Alavi 2021). Accurate measurement of indoor air quality is therefore essential for protecting people. However, indoor environments change continuously due to short-term events such as ventilation, changes in occupancy, and human activities (Wu et al. 2021). They also exhibit spatial heterogeneity, meaning that air quality can differ across locations even within the same indoor space (Li et al. 2018). Because of this temporal and spatial heterogeneity, a small number of sensors may fail to capture both local changes and the overall air quality distribution. Therefore, precise monitoring of indoor environments requires the dense deployment of high-accuracy sensors throughout the monitored space.

Deploying a dense network of high-accuracy reference sensors (i.e., high-cost sensors), however, is costly. Low-cost sensors can be deployed at lower cost, but their measurements are often affected by noise and drift, making them less accurate (Koziel et al. 2025). Hence, instead of installing reference sensors at every measurement point, calibrating low-cost sensors with a lightweight deep learning model to achieve near-reference accuracy can provide an alternative that balances cost and performance (Concas et al. 2021; Ahn et al. 2024; Dalbah, Worring, and Hsu 2026).

Low-cost sensor calibration models are trained using data collected from reference sensors. Under this conventional setting, termed strict pairwise calibration, at least one reference sensor is required at every location where a low-cost sensor is deployed (Yu et al. 2020; Ahn et al. 2025). However, deploying reference sensors at all locations makes effective indoor air quality monitoring prohibitively expensive.

Accordingly, practical indoor air quality monitoring requires a calibration method that can calibrate low-cost sensors across multiple locations using only a few reference sensors. Such a method must be robust to both rapid environmental changes and spatial heterogeneity. Addressing these practical requirements involves three key challenges: constructing a dataset representative of indoor environments, defining realistic evaluation scenarios, and designing an efficient and robust calibration model. Specifically, we focus on the following:

• Long-term, multi-location data: A sensor calibration dataset must capture spatial variations and temporal changes under limited reference-sensor availability.

• Realistic evaluation scenarios: Calibration must operate robustly under real-world deployment conditions, including at locations without reference sensors and under short-and long-term distribution shifts.

• Efficient and robust calibration: A lightweight calibration model must effectively generalize across locations and distribution shifts using limited reference data.

To address these challenges, we propose a benchmark for indoor sensor calibration. First, we construct a six-month, multi-location indoor air quality dataset comprising synchronized measurements from low-cost and reference sensors deployed at five locations in a university laboratory (Section 4). The dataset contains measurements of five environmental variables (i.e., CO2CO_{2}, CO, temperature, humidity, and PM1PM_{1}), along with metadata on door and window states, enabling the analysis of both gradual distribution shifts and rapid environmental changes. Based on this dataset, we define four evaluation scenarios that reflect limited reference-data availability, unseen-location generalization, and short- and long-term distribution shifts (Section 3). Guided by these scenarios, we derive five design requirements and propose a calibration

∗^{*}Corresponding author.

Table 1: Comparison of low-cost sensor calibration studies and datasets. T. and RH. denote temperature and relative humidity.

Dataset (Calibration Study)ModalitiesDataset PropertiesDeployment Scenarios
Indoor.MultiLoc.Event.S1S2S3S4
UCI Air Quality (Aula et al. 2022)CO, NO2NO_{2}, T., RH.×××××✓×
Author-collected (Allka et al. 2023)O3O_{3}, T.×✓×××××
Author-collected (Ahn et al. 2024)PM10PM_{10}✓✓×××××
Author-collected (Bachechi, Rollo, and Po 2024)NO, NO2NO_{2}, O3O_{3}×✓×××✓×
SensEURCity (Ahn et al. 2025)PM1PM_{1}, PM2.5PM_{2.5}, PM10PM_{10}×✓×××××
AQ-SDR (Dalbah, Worring, and Hsu 2026)PM2.5PM_{2.5}×✓×✓×✓×
Indoor Sensor Calibration (Ours)CO2CO_{2}, CO, T., RH., PM1PM_{1}✓✓✓✓✓✓✓

Dataset properties. Indoor. (indoor setting); MultiLoc.(multi-location data); Event. (event metadata). Symbols. Supported (√); not supported (×).

model designed to satisfy these requirements (Section 5). Our main contributions are summarized as follows:

  • Dataset: We construct a six-month, five-location indoor sensor calibration dataset with synchronized low-cost and reference sensor measurements and event metadata.

  • Scenarios: We design four practical scenarios for effective indoor sensor calibration, in which many low-cost sensors across multiple locations are calibrated using limited reference data under spatial and temporal shifts.

  • Model: We propose a lightweight temporal calibration model that robustly addresses scenario-driven design requirements with low edge-inference cost.

References (16)