arXiv(opens in a new tab)cs.AIOct 2026Cited by 1 paper on PaperVantage

Manuscript Offprint

arXiv:2610.09937

Where Can a Decision Model Diagnose HVAC Faults? Reasoning Demand, Physical Representation, and Robustness Under Shift

Wooyoung Jung

Abstract

Artificial intelligence supports building operations in several forms, each with its own barrier. Expert rules must be tuned for every system, supervised models need labeled data that buildings rarely record, and language models return free text that requires human-in-the-loop checking, since their stated confidence is unreliable. A newer kind of pretrained model, here called a decision model, returns a probability for every allowed answer, so one model could serve many decisions without training. This study answers three open questions for fault diagnosis in heating, ventilation, and air-conditioning systems: which decisions such a model can make, what input it needs, and whether its probabilities hold when conditions change. On 128 fault days from four public datasets of real equipment, faults are graded by the reasoning their diagnosis demands, with data given raw, as physical features, or with Brick topology. The decision model Jev, open language models, and a supervised model face nine tests that change season, control configuration, or building. Given physical features, Jev and the larger open model diagnosed faults whose evidence one feature carries, but not faults that need operating context. Under shift they kept their accuracy and calibration, while the supervised model lost 0.33 macro-F1 yet led or tied within a building. Their probabilities still needed correction, and detection was weak. The study maps which faults a decision model can diagnose and from what input, and supports a division of work in which code computes the physics and the model

∗^{*}Corresponding author.

Email address: wooyoung@arizona.edu (Wooyoung Jung) ranks candidate faults for an operator.

Keywords: fault detection and diagnosis, HVAC, decision model, training-free, calibration, distribution shift, Brick schema

1. Introduction

Artificial intelligence (AI) is moving into building operations on different scales and in various forms [1]. In fault detection and diagnosis (FDD), for example, expert rules such as the Air Handling Unit Performance Assessment Rules (APAR) flag faults from fixed relations among sensor readings [2, 3], and machine learning (ML) classifiers learn fault signatures from labeled operating data [4]. Beyond diagnosis, model predictive control (MPC) and reinforcement learning (RL) optimize how equipment is operated [5, 6]. MPC uses a model of the building to predict its response over the coming hours and chooses the setpoints that minimize energy use or cost while keeping occupants comfortable. RL learns a control policy by trial and error, rewarded for saving energy without sacrificing comfort. The newest forms are language based [7, 8, 9]. Large language models (LLMs) now help create and query semantic models of buildings from raw point names [10], generate building energy models from plain-language descriptions [11], explain the decisions of learned controllers to operators [12], and automate the development of MPC controllers for heating, ventilation, and air-conditioning (HVAC) systems [13]. In diagnosis, they mine operating data for faults and inefficiencies, either alone or guided by domain knowledge [14, 15].

Each of these forms carries its own burden. Rules must be written and tuned by experts for each system. Classifiers need labeled data from the system they serve, MPC needs a model of the building, and RL needs extended interaction with the building or a simulator of it. LLMs need no labels or building model, but they keep a human in the loop. They produce text, code, or a model, and a person or another program checks the result before anything acts on the building. The way they answer keeps them at this distance from the controls. Their output is free text, which software must parse and validate before acting on it. They can state plausible content that is wrong [16], and the confidence they express in words tends to exceed their accuracy [17]. Their answers also shift with the wording and order of a prompt [18], and each answer costs a full text generation, which is slow and expensive for decisions repeated every few minutes across many units.

A newer kind of model aims closer to the controls. Called here a decision model, it reads a description of a situation, called the state, together with a set of typed questions about it. Each question fixes its answer space in advance. It may ask for one choice among named options, a level on an ordered scale, or a yes or no. The model returns a probability for every allowed answer and cannot return anything outside that space [19]. In this it resembles a trained classifier. But the question and its answers are supplied with each request, so one model can serve many decisions without being trained on any of them. Jev, released in September 2026, is one such model. Its developer reports that it was trained so that its stated probabilities track how often it is right [19]. Independent evaluations appeared within days of its release [20]. One, on tasks outside buildings, found its probabilities well calibrated when pooled across tasks but not within a single task [21]. Its developer presents it as a model for fast judgment and advises doing arithmetic in code before the state reaches the model.

Building automation is full of such decisions. A supervisory controller must judge whether a zone is occupied [22, 23], whether outdoor air is suitable for free cooling, whether a sensor reading is plausible, and, most consequently, whether a unit is running normally or with one of a known set of faults. Each of these decisions has a fixed set of answers, recurs every few minutes on every unit, and feeds other software. A model that returns a trustworthy probability for every answer could serve this setting well. The probability could set an alarm threshold, rank maintenance work by likelihood, or pass an uncertain case to an operator. Before any such decision is delegated, three things must be known. The first is which decisions these models can make reliably. The second is what input they need, since a model built for fast judgment may falter on raw numbers that require calculation. The third is whether their probabilities stay trustworthy when the season, the equipment, or the building changes.

FDD in HVAC systems is a demanding test of these questions. A training-free model would be valuable there, because the two established routes stall on the same obstacle. Rules must be tuned by experts for each system, and classifiers need labeled faults that real buildings rarely record, while classifiers trained elsewhere must be adapted before use on new equipment [24, 25]. A model that diagnoses without training would remove that obstacle. The task is also hard for such a model, because diagnosis rests on physics. A stuck outdoor-air damper shows only after the outdoor-air fraction is computed from three temperatures and compared with the damper command, which is exactly the arithmetic that decision models are advised to leave to code. FDD also allows the question to be settled with evidence, since public datasets record faults imposed deliberately on real equipment [26, 27, 28]. Because a wrong diagnosis sends a technician to the wrong component or leaves a fault running, the trustworthiness of the stated probabilities matters as much as their accuracy.

Published evaluations of language models for FDD do not yet settle this question. Prompted without training, LLMs name some faults and miss others [14, 29], and fine-tuned models reach high accuracy, but only after training on labeled fault data [30, 31]. These studies report accuracy on data from the system and season used to build or prompt the model. They leave open whether the stated probabilities can be trusted, how performance changes when the season or the equipment changes, and which kinds of fault are within reach.

This study addresses three questions.

• RQ1, capability. Which faults can training-free models diagnose, and how does accuracy depend on the reasoning a fault demands?

• RQ2, representation. Does computing the physics in code first, as physical features, close the gap? Does adding the equipment topology and the latest value of every point help further?

• RQ3, robustness and trust. When the season, the control configuration, or the building changes, do training-free models lose less accuracy than a supervised model? Can their stated probabilities be taken at face value?

To answer them, this study assembles 128 fault days measured in four real buildings, three built for research and one occupied, all from public datasets. They cover a rooftop unit, three laboratory air-handling units (AHUs), and AHUs in an occupied university building. Each fault type is graded by the reasoning its diagnosis demands, from a single reading that departs from its command to a pattern that unfolds over time. Every 60-minute window is presented in four forms, ranging from raw sensor readings to physical features computed in code and the equipment's Brick topology. Jev, open language models at two sizes, and a rule-based reference diagnose every fault day without training. A supervised gradient-boosted model joins them in tests that shift the season, the control configuration, or the building. Accuracy, and how well the stated probabilities match observed accuracy, are measured in each case.

The study contributes a map of where a training-free decision model can and cannot diagnose HVAC faults, together with the input it needs and the trust its probabilities deserve when conditions change. The harmonized splits, labels, and reasoning-level assignments are available from the author on request.

References (63)