arXiv:2608.26021cs.DCAug 2026

Manuscript Offprint

arXiv:2608.26021

Slasher: Power Flexibility for Cloud Datacenters

Liuzixuan Lin, Fiodar Kazhamiaka, Alok Gautam Kumbhare, Chaojie Zhang, Jaylen Wang, Hassan Khan, Rodrigo L. Assis, Mariana Rodrigues, Kyle Woolcock, Nithish Mahalingam, Brijesh Warrier, Rodrigo Fonseca, Ricardo Bianchini

Liuzixuan Lin

University of Chicago

United States

Chaojie Zhang

Microsoft Azure

United States

Rodrigo L. Assis

Microsoft Azure

United States

Nithish Mahalingam

Microsoft Azure

United States

Fiodar Kazhamiaka

Microsoft Azure

United States

Jaylen Wang

Carnegie Mellon University

United States

Mariana Rodrigues

Microsoft Azure

United States

Brijesh Warrier

Microsoft Azure

United States

Ricardo Bianchini

Microsoft Azure

United States

Alok Gautam Khumbare

Microsoft Azure

United States

Hassan Khan

Microsoft Azure

United States

Kyle Woolcock

Microsoft Azure

United States

Rodrigo Fonseca

Microsoft Azure

United States

Abstract

Datacenters consume many megawatts of power, and regularly encounter scenarios that require modulating their power draw. These scenarios include datacenter infrastructure failures, power grid failures, grid services, and more, spanning a diverse range of requirements in terms of the power magnitude, the scope of the reduction, the notice time, and other dimensions. To address these scenarios, we have built Slasher, a general system for modulating the power of Azure datacenters to handle scenarios ranging from individual racks to regional multi-datacenter grid events. Slasher coordinates datacenter resources with the goal of meeting power targets while minimizing negative impact on hosted workloads.

In this paper, we review the main power modulation scenarios, characterize the power reduction levers using data from production cloud datacenters, describe Slasher's system architecture, and formulate the cloud datacenter power modulation control problem. We also develop a high-fidelity datacenter simulator and propose a workload impact model, using them to design and evaluate power control algorithms.

CCS Concepts: • Applied computing → Data centers; • Hardware → Power and energy.

Keywords: Datacenter power management

1 Introduction

Cloud datacenter sites require 10s-1000s of MW of power capacity, contributing a meaningful and rapidly growing fraction of demand on power grids [5, 12, 24, 48]. In the existing paradigm, datacenters expect to always consume as much power as they need, up to a limit defined in the contract with the grid operator. This paradigm is showing signs of a shift, affected by the trends of increased demand for power-hungry AI applications, and the scarce power capacity in the grids where datacenters are being deployed. At a time of rapid growth desired by cloud providers and their customers, new datacenter deployments are being deprioritized [54] and postponed [10]. In power-constrained regions, new requirements are emerging for datacenters to dynamically reduce power to support the grid [3, 8, 14, 15, 44]; power flexibility is expected to unlock 10's of GW of capacity within existing infrastructure [38].

Datacenter power flexibility - the ability to change power draw on demand - is an increasingly important function that involves many scenarios, levers, triggers, goal states, and impacts. Flexibility scenarios can have external triggers, such as grid failures and demand response programs [3, 13, 16], or internal triggers, such as maintenance and failures of cooling/power equipment [9, 47]. Each scenario can vary significantly in the magnitude of power reduction, how often it occurs, the reduction domain, the event duration, and the amount of advance notice time. For example, a cooling failure may require a 10% power reduction in an entire data hall for 3-6 hours while equipment is repaired, with 30 minutes of thermal inertia lead time; in contrast, a concurrent fault across multiple rows may require a near-instant reduction of 5% power across a subset of affected datacenter power domains to prevent cascading failure.

In a public cloud datacenter, power is dictated by many thousands of servers, each typically hosting one or more virtual machines (VMs), each of which might run one of many thousands of applications, into which the cloud platform has limited visibility. This limits cloud datacenter operators from broadly adopting power management policies that leverage application flexibility to reduce power, a topic that has been extensively explored in the literature[27, 32, 49, 51]. Instead, operators must rely on data from the platform and power devices, such as server occupancy, resource utilization telemetry from servers, and power telemetry from meters across the power delivery system.

A multitude of software- and hardware-based levers for power modulation exist across hierarchies of power and IT components within datacenters, including power devices such as generators and batteries; hardware control levers such as server throttling and shut-down; platform levers that manage the state of VMs; and application levers such as workload migration and delay.

Although these levers can effectively shed power in most scenarios when applied individually, each lever has notable financial, performance, and utilization limitations when employed in isolation. Further, these levers differ in how much power they can reduce, for how long, and with what advanced notice they can operate. For example, batteries are expensive when provisioning enough to handle hours of datacenter load, and the use of fossil-fuel (typically diesel) generators is regulated and sometimes prohibited from being used for prolonged periods [11]. Levers that involve VMs and servers can impact application metrics and risk violating Service Level Objectives (SLOs) [58, 60]. Overall, cloud datacenters present a large and complex action space for power modulation, where the primary challenge is to satisfy a wide range of scenarios while minimizing the negative impact on hosted workloads.

To manage power and support emerging scenarios, we have built Slasher: a general system for datacenter power flexibility. Slasher manages the power consumption of Microsoft Azure datacenter infrastructure through a combination of power devices and software platform levers, and explicitly minimizes impact to hosted services while meeting power targets. For each supported scenario, Slasher uses a modulation policy to compute a playbook: a table mapping levers to specific power domains. When a scenario is triggered, Slasher activates a playbook to modulate power to within the scenario's power target. Playbooks are periodically recomputed to adjust to the dynamic state of the datacenter.

Computing power shedding playbooks involves dealing with a large optimization space of power reduction actions, inter-dependencies, and power implications. To experiment with control policies for Slasher, we have built Stratosim, a datacenter simulator to replay datacenter power telemetry at the granularity of VMs. Stratosim enables testing of policies that deploy any combination of power shedding levers. To study the power modulation control problem, we analyze a variety of cloud server and service metrics, and propose a general impact model based on capacity and load to estimate the risk of SLO violations caused by power shedding actions for common cloud applications. We express impact at the scale of a service: a set of one or more VMs that compose a cohesive element of an application. The impact functions are designed to be a faithful proxy to the risk and magnitude of SLO violation caused by power reduction levers, and leverage the (limited) visibility into applications, such as grouped VM deployments, VM size, and resource utilization telemetry.

The development of Slasher is ongoing and evolving. The core system and mechanism are operational and in production, but some levers and scenarios described in this paper are still being integrated. In addition, GPU- and LLM-specific workload management is ongoing work and not discussed in this paper. Although there are opportunities for power modulation [30, 42, 43, 46, 50] when these workloads are present, these techniques require application visibility and control that is generally not available at the platform layer. Such application-specific power modulation would require direct interaction between platform and workload. This paper focuses on addressing the challenges of managing public cloud datacenters at the platform layer, leaving platform-workload interaction as future work.

Our contributions are as follows:

• Analysis of the scope of power reduction from production traces at Microsoft;

• Design of Slasher, a general system for modulating datacenter power;

• Results of a live experiment of coordinated battery and workload management for power reduction

• Stratosim, a high-fidelity DC power simulator 1^{1};

• A general workload impact model, and formulation of the impact-minimization power control problem.

• Simulation-based experiments of several Slasher control policies.