Time-series Foundation Models for Predictive Control: The Role of Excitation

Mazen Amria, Jasper Hoffmann, Philipp Bordne, Anna Rothenhäusler, Lilli Frison, Harald Taxt Walnum, Sebastien Gros, Joschka Bödecker

Abstract

Deploying model predictive control (MPC) requires constructing or identifying a predictive model for each target system. Time-series foundation models (TSFMs) offer an attractive option thanks to strong zero-shot forecasting capabilities across systems. However, low forecast error does not guarantee that a TSFM captures the system's response to the alternative actions considered by the controller. We study this gap using residential heat-pump control as a test bed, measuring the agreement between predicted and ground-truth effects of control interventions. Importantly, we find that TSFMs can recover the system's input–response relationship when the context contains sufficient independent control excitation. Common fine-tuning pipelines and feature smoothing reduce, but do not eliminate, the need for in-context excitation. Our results indicate that current TSFMs used for predictive control require sufficiently informative control variation in the inference context. Initial closed-loop results show promise for shorter context windows.

1 Introduction

Time-series foundation models (TSFMs) have emerged as strong zero-shot forecasters, with impressive transfer across datasets and domains [1]. This makes them promising dynamic models for model predictive control (MPC), potentially avoiding the need to construct or identify a model specifically for each target system. However, forecasting accuracy alone is not sufficient for control. Standard forecasting evaluates predictions on trajectories generated by a fixed controller that produced the training data, whereas MPC queries the model under candidate control inputs that may differ substantially from those observed. A model may therefore achieve low forecasting error by capturing passive dynamics, exogenous disturbances, or regularities of the data-generating policy, without correctly modeling the effect of out-of-distribution control inputs. Effective planning instead requires separating the effect of a control input from these of other sources of variation.

Replacing system-specific identification with a transferable pretrained model is particularly attractive in building energy management, where predictive control can require substantial effort to construct and identify system-specific models. Building thermal dynamics vary across systems and operating conditions, are strongly influenced by disturbances such as weather and occupancy, and are observed through heterogeneous sensing, actuation, and control hardware. Thus, such systems are intrinsically stochastic and only partially observed. In this setting, data-driven linear multi-step predictors can be effectively integrated into MPC frameworks [2]. On real-world building data, however, modern TSFMs can achieve substantially better nominal forecasting performance. As shown in Fig. 1, zero-shot Chronos-2 [3] outperforms a multi-step linear predictor for both room-temperature and heat-pump power forecasting across context lengths.

Correspondence to: Mazen Amria amriam@cs.uni-freiburg.de

40th Conference on Neural Information Processing Systems (NeurIPS 2026). Workshop: TS-LIMITS.

Approx. Linear Dynamics: Room Temperature

Figure

context length [d]

Nonlinear Dynamics: Heat-Pump Power

context length [d]

Figure 1: Strong zero-shot forecasting on real-world building data. Average MAE of Chronos-2 [3] and a multi-step linear predictor for approximately linear room-temperature dynamics and nonlinear heat-pump power dynamics across context lengths. See Appendix A for details.

Yet this forecasting advantage does not imply that the model captures the input-output relationships required for control. Previous work has raised concerns about this distinction. At the same time, recent TSFMs such as Chronos-2 [3] provide richer conditioning mechanisms, including known future covariates and multivariate forecasting. These developments motivate a more systematic evaluation of recent TSFMs's ability to capture control-relevant input-response behavior rather than merely predicting trajectories accurately under the data-generating distribution.

We investigate this distinction in residential heat-pump control, using it as a controlled test bed for separating forecasting performance from control-relevant dynamics. We construct matched intervention probes in which the initial state and disturbances are held fixed while the future supply-temperature trajectory is varied, allowing us to assess nominal forecast accuracy independently from input-response fidelity. We further study whether input-response fidelity can be improved through fine-tuning on independently excited trajectories, excitation in the inference context, and multiscale representations of the control input.

Our contributions are threefold: (i) we find that, in simplified synthetic experiments and under certain conditions, TSFMs can identify the control-relevant input-output relationship; (ii) we show that fine-tuning on closed-loop operational data improves predictions of the response to alternative controls, with greater improvements when fine-tuning on excited data, while leaving nominal forecasting accuracy along the factual control trajectory largely unchanged; and (iii) we show that excitation in the inference context is a main mechanism enabling system identification, while fine-tuning provides a complementary prior that reduces the amount of informative excited context required when transferring to unseen buildings, but does not eliminate the need for excitation.