arXiv:2609.09564cs.LGSep 2026

Manuscript Offprint

arXiv:2609.09564

Robust Industrial Cyber Physical Classification Using Neuromorphic Temporal Embeddings and Hybrid SNN XGBoost Under Machine Unlearning Attacks

Ammar Kamoona, Sajad Koushkbaghi, Mahdi Jalili, Peter McTaggart, Xinghuo Yu

Open access. PaperVantage converted this article to text, so layout and figures may differ from the original.

Ammar Kamoona ID^{ID}, Sajad Koushkbaghi ID^{ID}, Mahdi Jalili ID^{ID}, Member, IEEE, Peter McTaggart ID^{ID}, and Xinghuo Yu ID^{ID}, Senior Member, IEEE

Abstract—The digitalisation of electrical distribution networks has increased the exposure of power-grid infrastructure to cyber attacks. Existing intrusion detection systems (IDSs), however, often rely on computationally expensive deep learning models that are difficult to deploy at the edge. Periodic retraining also exposes these systems to machine unlearning attacks, where selective data removal can degrade detection performance. We propose a hybrid Spiking Neural Network (SNN) and XGBoost architecture that combines efficient temporal encoding with a lightweight classifier and provides structural resilience to such attacks. The SNN is trained once on clean data and used as a fixed feature extractor, while only the XGBoost classifier is retrained during model updates. Evaluated on two real-world public power-system datasets, the proposed method achieves 99.9% accuracy (F1-macro 0.999) on the Synchrophasor dataset and 95.0% accuracy (F1-macro 0.943) on the MSU/ORNL dataset, outperforming standalone baselines. Under selective label-flipping attacks, the hybrid model loses only 0.9% F1-macro at 10% poisoning and delays target-class collapse from 60% to 70% poisoning compared with raw models. These results demonstrate that neuromorphic temporal encoding can provide both accurate cyber-attack detection and improved resilience to data poisoning in cyber-physical systems.

Index Terms—Spiking neural networks, intrusion detection systems, power grid cybersecurity, machine unlearning, false data injection, neuromorphic computing, surrogate gradient learning

I. INTRODUCTION

ELECTRICAL distribution networks are increasingly evolving into interconnected cyber-physical systems as distributed energy resources and advanced control technologies become more widely integrated, resulting in reliance on intelligent electronic devices (IEDs) such as remote terminal units (RTUs) and phasor measurement units (PMUs), and communication networks for monitoring, protection, automation, and control. [1]. While these technologies enable more flexible and efficient operation, they also increase the dependence of distribution networks on digital infrastructure and communication networks. Consequently, vulnerabilities in cyber components can affect the operation of physical grid assets, making cybersecurity an integral component of the reliability and resilience of modern distribution networks [2].

Cyber attacks against power-system cyber-physical infrastructure can target both the information used to monitor and control the physical system and the communication mechanisms through which this information is exchanged. False data injection (FDI) attacks alter measurement data to provide misleading information about the state of the power system, potentially compromising monitoring and state-estimation functions [3]. In synchrophasor-based monitoring, time-synchronisation attacks (TSAs), particularly those based on GPS spoofing, can manipulate the timing information used to synchronise measurements, potentially compromising monitoring and control functions [4]. At the communication layer, attacks can exploit power-system communication protocols to inject, replay, or manipulate messages, potentially disrupting the exchange of information between IEDs. Such attacks are particularly relevant to IEC 61850-based substations, where GOOSE messages support time-critical communication for protection and automation functions [5].

Since cyber attacks can have a widely diverse nature and manifest across various aspects of a cyber-physical power system, their accurate detection is a challenging task. Furthermore, an effective intrusion detection system should not only identify whether an attack has occurred, but also classify its type, providing more informative awareness for subsequent response and future mitigation. When it comes to the practical implementation of a detection system, minimal computational overhead and low latency are important, particularly when monitoring must be performed continuously and close to the physical infrastructure. Moreover, practical detection systems may need to accommodate heterogeneous data sources, ranging from continuous-valued electrical measurements to structured communication traffic generated by grid protocols [6].

Existing cyberattack detection approaches for power systems broadly include rule- and signature-based methods [7], model-based methods that exploit knowledge of system dynamics and operating constraints [8], and data-driven methods that learn attack characteristics from observed data [9]–[13]. Rule- and signature-based methods rely on predefined thresholds, rules, or known attack signatures and therefore require the relevant attack behaviors to be specified in advance [14]. Model-based approaches can exploit physical knowledge of the grid and provide interpretable detection decisions, but their effectiveness can depend on the availability and fidelity of the underlying system model and can be affected by mod-

Ammar Kamoona, Sajad Koushkbaghi, Mahdi Jalili, and Xinghuo Yu are with the EV Living Lab, RMIT University, Melbourne, VIC, Australia (e-mail: ammar.kamoona@rmit.edu.au; sajad.koushkbaghi@rmit.edu.au; mahdi.jalili@rmit.edu.au; xinghuo.yu@rmit.edu.au). Peter Mctaggart is with Powercor, Melbourne, VIC, Australia.

eling uncertainties and changing operating conditions [15]. Data-driven approaches provide an alternative by learning attack-related patterns from measurements or communication data, thereby reducing reliance on manually specified attack signatures and detailed physical models. Deep learning methods have consequently been investigated for detecting cyberattacks from complex power-system measurements and communication data, with architectures such as convolutional, recurrent, and graph neural networks [16]–[19]. However, the computational and memory requirements of conventional deep learning models can impose constraints on low-latency and resource-efficient deployment.

Spiking neural networks (SNNs) offer an alternative neural computing approach in which information is represented through discrete spike events and processed according to the temporal dynamics of spiking neurons [20], [21]. Their event-driven operation and sparse activity offer the potential for computationally and energy-efficient processing, while their intrinsic temporal dynamics make them suitable for analysing sequential signals. These characteristics have motivated the application of SNNs to intrusion detection and power-system security, including dynamic FDI attack detection and network intrusion detection [22]–[26]. However, existing SNN-based approaches have primarily focused on detection performance, network architecture, or energy efficiency, while the resilience of their learned representations to training-time data manipulation, such as malicious machine unlearning, remains largely unexplored. Training-time poisoning attacks can manipulate the learned decision function by corrupting training samples or labels [27], highlighting the need to consider the resilience of the detection systems' training data pipelines in addition to their ability to detect cyberattacks.

To address this vulnerability, we propose a hybrid SNN–XGBoost architecture that separates representation learning from classifier adaptation. A Direct-SNN with Leaky Integrate-and-Fire (LIF) neurons processes sliding windows of PMU measurements and generates temporal membrane-potential embeddings, while a lightweight XGBoost classifier is periodically retrained on these fixed embeddings to accommodate evolving operating conditions. The SNN is trained once using verified clean data during system commissioning and subsequently frozen, preventing label manipulation during classifier retraining from altering the learned feature representation. Because the membrane-potential embeddings capture temporal characteristics of the underlying electrical signals rather than classifier labels, poisoned samples remain constrained by the physical structure encoded by the frozen feature extractor.

The main contributions of this paper are as follows:

  1. We show that the proposed hybrid SNN+XGBoost architecture achieves state-of-the-art detection accuracy on two real power grid datasets: 99.9% (F1-macro 0.999) on the Synchrophasor dataset and 95.0% (F1-macro 0.943) on the MSU/ORNL dataset, outperforming all standalone baselines.

  2. We demonstrate that the proposed method provides inherent robustness against machine unlearning attacks. At 10% label poisoning, the hybrid loses only 0.9% F1-macro and delays target-class collapse from 60% to 70% poisoning compared to raw feature models.

  3. We provide a mechanistic explanation: SNN membrane potential embeddings encode physical signal structure (i.e., the temporal dynamics of voltage and current measurements) that is invariant to label corruption.

  4. We propose a secure deployment architecture that separates the frozen feature extractor from the periodically updated classifier, providing defence-in-depth against training data poisoning.

  5. We present experiments on the MSU/ORNL dataset (78,377 samples, 128 PMU features) comparing the hybrid against raw XGBoost and Random Forest at 10 attack levels (0–90%).

The rest of this paper is organised as follows. Section II reviews related work. Section III presents the theoretical foundations. Section IV describes the proposed method. Section V provides experimental setup and Section VI provides the results and the discussion. Section VII concludes the paper.

References (43)